24 RCM410R-x_D00403_01_M_XXEN/09.2020
Modbus settings
Address
(dec)
Register name Data type Bytes Mode Value/Unit/Comment Factory
setting
Function 4: Reset to factory settings/Reset
parameters
60000 Function selection Uint16 2 WO 4 → Selection of "Reset to factory
settings/Reset parameters" function
N/A
60001 Pattern value part 1 Uint16 2 WO 62663 → Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2 Uint16 2 WO 1304 → Safety pattern must be written
for the function to be executed
N/A
60003 Type of reset Uint16 2 WO 1 → Reset to factory settings excluding
interface parameters
2 → Reset to factory settings including
interface parameters
N/A
Function 6: Test
60000 Function selection Uint16 2 WO 6 → Selection of the "Test" function N/A
60001 Pattern value part 1 Uint16 2 WO 32343 --> Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2 Uint16 2 WO 0 → Safety pattern must be written for
the function to be executed
N/A
60003 Type of test Uint16 2 WO 3 → Start RCM test N/A
Function 7: Reset
60000 Function selection Uint16 2 WO 7 → Selection of "Reset" function N/A
60001 Pattern value part 1 Uint16 2 WO 13623 → Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2 Uint16 2 WO 0 → Safety pattern must be written for
the function to be executed
N/A
60003 Type of reset Uint16 2 WO 1 → Reset of the alarm message when
fault memory is enabled
N/A