Operation and setup
33
RCMA423-DM_D00064_03_M_XXEN/06.2017
5.5.9 Setting the 100 % reference for the analogue interface
Set here whether the 100% value of the output signal is to be coupled to the
response value I2 (I
n2
) (AL) or to a freely configurable value. A configurable
value range from 30mA to 3A is available.
Factory setting = coupling to response value I2 (I
n2
) (AL).
The following example shows the modification of the 100% reference of
AL = coupling to response value
on a 100% value of 60 mA.
3x
>1,5 s
5x