39
RCMA423-DM_D00064_03_M_XXEN/06.2017
6. Technical data
6.1 Tabular data
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
RCMA423-DM-1:
Rated insulation voltage.................................................................................................................. 100 V
Overvoltage category/pollution degree ............................................................................................III/3
Rated impulse withstand voltage.................................................................................................. 2.5 kV
RCMA423-DM-2:
Rated insulation voltage................................................................................................................. 250 V
Overvoltage category/pollution degree ............................................................................................III/3
Rated impulse withstand voltage..................................................................................................... 4 kV
Supply voltage
RCMA423-DM-1:
Supply voltage range U
s
........................................................................... AC 24…60 V/DC 24…78 V
Operating range supply voltage U
s
......................................................... AC 16…72 V/DC 9.6…94 V
Frequency range U
s
...................................................................................................... DC, 42…460 Hz
RCMA423-DM-2:
Supply voltage range U
s
.......................................................................................... AC/DC 100…250 V
Operating range supply voltage U
s
........................................................................... AC/DC 70…300 V
Frequency range U
s
...................................................................................................... DC, 42…460 Hz
Protective separation (reinforced insulation) between......................................... (A1, A2) - (k/l, T/R) - (M+, μA, V)
Voltage tests according to IEC 61010-1.............................................................................................................. 2.21 kV
Power consumption ..........................................................................................................................................≤ 6.5 VA
Measuring circuit
External measuring current transformer type............................ W20AB, W35AB(P), W60AB(P), W120AB, W210AB
Rated insulation voltage (measuring current transformer) ..................................................................................800 V
Operating characteristics acc. to IEC 62020 and IEC/TR 60755............................................................................ type B
Rated frequency......................................................................................................................................... 0…2000 Hz
Measuring range AC/DC.............................................................................................................................. 3 mA…6 A