3. Function
3.1 Device features
Undervoltage and overvoltage monitoring of AC/DC systems 0…300 V
in the frequency range DC/15…460 Hz
Preset function: Automatic response value setting for undervoltage
and overvoltage, < U and > U as well as for underfrequency and over-
frequency < f and > f.
Voltage and frequency monitoring with window discriminator func-
tion, < U and > U as well as < f and > f.
Indication of the system frequency f
Start-up delay, response delay and delay on release
Adjustable switching hysteresis for U and f
r.m.s. value measurement AC + DC
Measured value display via multi-functional LC display
Alarm indication via LEDs (AL1, AL2) and changeover contacts (K1, K2)
N/C operation or N/O operation selectable
Password protection against unauthorised parameter changing
Fault memory can be deactivated. In the
"con“ mode, all alarm parameters remain stored on failure of the supply
voltage.
Start-up of the device with or without simulated alarm message
Frequency alarm behaviour in case of measuring voltage failure can be
parameterised