EasyManua.ls Logo

Bender VME420 - 6 Technical Data VME420; Data in Tabular Form

Bender VME420
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data VME420…
43
VME420_D00026_03_M_XXDE/04.2019
6. Technical data VME420…
6.1 Data in tabular form
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage ....................................................................................................................................... 250 V
Rated impulse voltage/overvoltage category....................................................................................................4 kV / III
Pollution degree..............................................................................................................................................................3
Protective separation (reinforced insulation) between:........... (A1, A2) - (U1/+, U2/-) - (11-12-14) - (21-22-24)
Voltage test acc. to IEC 61010-1 ....................................................................................................................... 2.21 kV
Supply voltage
VME420-D-1:
Supply voltage U
s
............................................................................................. AC 16…72 V / DC 9.6…94 V
Frequency range U
s
....................................................................................................................... 15…460 Hz
VME420-D-2:
Supply voltage U
s
................................................................................................................. AC/DC 70…300 V
Frequency range U
s
....................................................................................................................... 15…460 Hz
Power consumption ........................................................................................................................................... 4 VA
Measuring circuit
Measuring range (r.m.s.) ................................................................................................................. AC / DC 0…300 V
Rated frequency f
n
.............................................................................................................................. DC, 15…460 Hz
Display, frequency range ...................................................................................................................... 10…500 Hz**
Response values
Undervoltage < U (Alarm 2) ........................................................................................................... AC / DC 6…300 V
Overvoltage > U (Alarm 1) ............................................................................................................. AC / DC 6…300 V
Resolution of setting U 6.0…49.9 V .................................................................................................................... 0.1 V
Resolution of setting U 50…300 V ......................................................................................................................... 1 V
Preset function:
Undervoltage < U = (0.85 U
n
):*
for U
n
= 230 V / 120 V/ 60 V/ 24 V ............................................................................... 196 V / 102 V / 51 V / 20.4 V
Overvoltage > U = (1.1 U
n
):*
for U
n
= 230 V / 120 V/ 60 V/ 24 V ............................................................................... 253 V / 132 V / 66 V / 26.4 V

Table of Contents