Technical data VME420…
48
VME420_D00026_03_M_XXDE/04.2019
6.4 User settings (overview)
Menu Parameter FAC User setting Setting range AL-LED
AL
U< ON V
PRESET or
6…300 V
2 *
U> ON V 1 *
U Hys 5 % % 1 … 40 %
Hz < OFF Hz
PRESET or
10…500 Hz
1+2 *
Hz > OFF Hz 1+2 *
Hz Hys 0.2 Hz Hz 0.1… 2.0 Hz
<U_Hz ON ON / OFF
out
M ON ON / OFF / CON
1n.o.
n.o. or n.c.
2n.c.
LEd OFF
ON / OFF
1/2 **
r1
1 Err OFF
r1 U< OFF
r1 U> ON
r1 Hz< ON
r1 Hz> ON
1 S.AL OFF ***
r2
2 Err OFF
r2 U< ON
r2 U> OFF
r2 Hz< ON
r2 Hz> ON
2 S.AL OFF ***
t
ton 1
0 s
s
0 … 300 s
ton 2 s
ts
toff s
Set Lock OFF 0…999
* only when LEd = off, ** only when LEd = on, *** depending on LEd setting