Memory When the FAULT status ends, FAULT memorisation will be signalled by
blinking on the associated LED.
Reset The RESET button will force all the FAULT Outputs into Standby status
and will delete the FAULT memory.
+
Standby status will be restored on a FAULT Output when the FAULT sta-
tus ends. However, if the FAULT is on the Output itself; it will be necessary
to RESET the control panel.
Functioning in the event of ALARM
FireClass100 can be programmed to go into WARNING status or PREA-
LARM status, before actually going into ALARM status.
WARNING status The WARNING status signals that an Input Point has exceeded the pro-
grammed Warning Threshold, and if the condition continues, will go into
ALARM status. Stop (Inhibit) the alarm procedure in the event of false
alarm. The WARNING status will be signalled by:
Ø the following message on the control panel and Repeater displays:
Ø the Output Points programmed as Warning Outputs;
Ø the FC200/COM Telecom Module ---- that when properly programmed will
call the programmed telephone numbers.
Press the ESC key to access the logger and view the most recent event
(see "Logger" paragraph).
PREALARM
status
The PREALARM status signals that an Input Point has exceeded the
Alarm Threshold. The control panel will not go into ALARM status until the
programmed PREALARM Time ends. However, an ALARM status will be
generated if another Input Point goes into ALARM status during the PREA-
LARM Time.
The PREALARM Time allows the User to check for False Alarm.
The PREALARM status is signalled by:
Ø the following message on the display:
Panel
in
WARNING
state !
USER GUIDE 13