Disable
The Disable option from the MODIFYING menu can be used to Disa-
ble/Enable Devices, Zones and Bell Outputs. This option is dealt with in
detail in the "MODIFYING" chapter.
The DISABLED LED will go ON when a Device is Disabled. ALARMS and
FAULTS etc. will not be signalled for Disabled Devices.
Alarm verify
The FireClass100 control panel can check the veracity of an ALARM sta-
tus from the moment it occurs.
When Alarm Verify is programmed for a Device the control panel will ge-
nerate an ALARM status in accordance with the Verify Time and the Veri-
fy Counter.
The control panel will hold Standby status for the entire time of the Alarm
Verify operation (Scanning Loops).
The number of Alarm Verify operations performed for an Input Point can be
viewed by means of the Dev./Zones/Outputs option from the READINGS
PARAMETER menu (see V).
Logger
The FireClass100 logger records the data of the last 200 events.
The logger is dealt with in detail in the "READING PARAMETERS" para-
graph.
Extinction Modes
To satisfy the strict Safety regulations for water and gas extinction me-
thods, each FireClass100 Output may be programmed as an "EXTIN-
CTION OUTPUT".
+
When an ALARM status is generated by a Device associated to an Extin-
ction Output, the Extinction Output in question will not be activated until the
programmed delay ends.
Inhibit Extinction Press any Inhibit Extinction button to add a further delay to the program-
med delay running on the Extinction Outputs. The effect the Inhibit Extin-
ction command will have on the the running delay depends on the pro-
grammed mode:
Ø ADD mode - the Extinction Inhibition adds 90 seconds to the programmed
Delay;
18 Analogue Fire Control Panel FireClass100