Ø STOP mode - the Extinction Inhibition will stop the Delay 10 seconds befo-
re the end. When the Extinction Inhibition is disabled the Delay will restart
and run for 10 seconds;
Ø FULL mode - the Extinction Inhibition will restore the Delay to its initial va-
lue. When inhibition is disabled the Delay will restart and run for the full De-
lay time.
Silence Press the SILENCE button to:
Ø block the running Extinction Output delay.
Ø force activated Extinction Outputs into Standby status.
Ø reactivate Extinction Outputs - forced into Standby status by the SI-
LENCE button. These Outputs will be reactivated after the programmed
delay.
+
In NIGHT Mode - the Silence status (block delay and force standby) will be
held for the programmed Silence Time;
Ø In DAY Mode - the Silence status (block delay and force standby) will be
held until the SILENCE button is pressed again.
Ø In both modes - Silence status will be overridden automatically if a new
ALARM or FAULT condition occurs.
Manual
Extinction
Press any Manual Extinction button to activate all Extinction Outputs wi-
thout delay.