46
◊ Value range: 0–5 Default: 1
By means of appropriate programming, the open collector output is capable of reacting to
one of the 10 conditions listed below.
NOTE: When automatic fault reset and restart are used (
68-NRST
), a fault greater than F10
will not be indicated until
69-DRST
has been exceeded.
Maximal load: 24 VDC, 50 mA.
◊ Value range: 0–10 Default: 7
The relay furnished with the inverter may be programmed to respond to any of the 10 con-
ditions listed below:
3 Output proportional to inverter load (
15-LOAD
), with full scale at 200% of rated
load.
4 Output proportional to output voltage (
13-VOUT
), with full scale at 100% of input
voltage.
72-ST1 – Open Collector Output ST1 1P
DATA
CODE
DESCRIPTION
0 Off.
1 Ready. The output becomes active when the inverter is ready. It is inactive in
Fault, Low Voltage, Idle and Program modes.
2 Fault. The output becomes active on Fault. See Note below.
3 Motor running Forward or Reverse, and output frequency above 0.5 Hz.
4 Motor running Reverse, and output frequency above 0.5 Hz.
5 Motor running Forward, and output frequency above 0.5 Hz.
6 Motor Speed = less than 0.5 Hz.
7 Motor at commanded speed.
8 Motor speed greater than preset speed
36-F5
.
9 In Torque Limit.
10 Over temperature warning. Temperature is within 10 °C of maximum tempera-
ture.
75-STR – Auxiliary Relay Output 1P
DATA
CODE
DESCRIPTION
0 Off.
1 Ready. The relay becomes active when the inverter is ready. It is inactive in
Fault, Low Voltage, Idle and Program modes.
2 Fault. The relay becomes active on Fault. See Note below.
3 Motor running Forward or Reverse, and output frequency above 0.5 Hz.
4 Motor running Reverse, and output frequency above 0.5 Hz.
5 Motor running Forward, and output frequency above 0.5 Hz.
6 Motor Speed = less than 0.5 Hz.
DATA
CODE
DESCRIPTION