EasyManua.ls Logo

Bernard Controls AQ Series - Heating element; TRAVEL LIMIT SETTINGS; Single cam setting

Bernard Controls AQ Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
11
5.4 Heating element
Each actuator includes a heating resistor.
As soon as the actuator is installed in the field, it is recommended
to power the resistor to prevent condensation.
ensuring its seal is clean.
components without their protection cover.
In case of water intrusion:
Dry electrical components before putting back the cover.
Check electrical insulation.
6 TRAVEL LIMIT SETTINGS
The actuator is factory-set for a 90°travel.
It features 2 devices to limit the travel:
Cams trigger switches to switch off power at an end position or
to signal a position
Mechanical stops mechanically block rotation to protect the valve
in case of over-travel. They must not be used as travel limits.
Single cam setting
The cam rotates with the
output shaft and
triggers a switch by
pushing on its lever.
Cams orientation are factory
pre-set, yet you can still
re-adjust them
during
the commissioning
if necessary.
Rep. Function Status before installation
1
Clockwise travel limit
Pre-wired, cam pre-set
2
Counter-clockwise travel limit
Pre-wired, cam pre-set
3
Clockwise signaling
To wire, to set
4
Counter-clockwise signaling
To wire, to set
12

Table of Contents

Related product manuals