EasyManua.ls Logo

Biddle HR 25 - Page 33

Default Icon
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HR MANUAL INSTALLATION
Manual version 4.1 (26-07-2018)
en-33
en
Calibrate the extract fan:
1. Set the unit to ‘manual’ and to ventilate
K via the home
screen of the b-touch control panel.
2. In the b-touch control panel, open the fu
nction
menu
> Maintenance > Calibrate air volume.
3. Enter the PIN code and press .
4. Calibrate the extract fan:
Caution:
c Adjust the highest speed (3) maximally to the
capacity of the unit (2500/3500/4500 m3/h).
For cooling with a cooling module use 500 m
3
/h less
(2000/3000 m
3
/h).
Note:
n Use the pressure difference meter over the extract
fan 5 .
Note:
n Use the chart to establish which pressure difference
gives the required flow rate.
Make sure to use the curve for the unit type that is
being used. (See type plate.)
Note:
n Always set all three settings. Even if you only want to
change one setting.
- Set all and any connected ventilation units to the set-
ting appropriate to setting 1 (low) of the HR unit.
- Set the desired flow rate for setting 1 (low) by adjust-
ing the percentage until the appropriate pressure differ-
ence is reached.
- Store by pressing .
- In the same way, set the desired flow rate for setting
2
(medium) and setting 3
(high).
- Check if all speeds are set correctly.
Note:
n Note the flow that is used for fan speed 3 of the
extract fan. This will be used later to calibrate the
pressure switch.