BIFFI FAIL SAFE ELECTRIC ACTUATORS, MODEL EFS2000V4
InstructIon and operatIng Manual
10.3 Description of variables and reports
Torque: Output torque in % of the nominal torque stated in the NAMEPLATE menu
Motor speed: RPM of electrical motor
Main voltage: Voltage (V) and frequency (Hz) of mains
Current: Current (A) absorbed by the motor
Temperature: Temperature (°C), inside the electronic compartment
Time: Present time
Date: Present date
Alarm: List of present alarms (see chapter ‘Maintenance’ and ‘Troubleshooting’)
Warning: List of present warnings (see chapter ‘Maintenance’ and ‘Troubleshooting’)
Ktemp: Temperature factor
Mot temp: Temperature (°C) of the electrical motor
Term temp: Temperature (°C) inside the terminal board compartment
Log status: Data logger status (off, ready, in progress: E: event number - n° of memory cycle or R: sample number - n° of memory cycle)
Wireless report: Bluetooth™ interface status (available, not available)
Node report: Report of BUS interface card (only present if the bus card is present) (see the relevant instruction manual)
FDI report: Report of FDI function (only present if the LonWorks bus card is present) (see the relevant instruction manual)
Base report: Base card report
• Card code
• Manufacturing week and year
• Electrical diagram, etc
Term report: Terminal board card report
• Card code
• Manufacturing week and year
• Electrical diagram, etc
Ain/aout report: Ain/Aout card report (only present if the card is present)
• Card code
• Manufacturing week and year
• Electrical diagram, etc.
EFS report: EFS card report
• Card code
• Manufacturing week and year
• Electrical diagram, etc
• EFS status: ready, not ready
• Base-EFS error counter
• Coil of clutch: ON,OFF
• Manual switch: AUTO, MANUAL
• Last PST result: passed, reset, failed, OV-TR, T-PST, T-RET
• Next PST: date
• Temperature: °C
• Mushroom push button: ON, OFF
• Heater: ON, OFF
• T-PST: (T-PST-baseline), last-T-PST, in sec
• T-RET: (T-RET-baseline), last-T-RET, in sec
• OV-TR: (OV-TR-baseline), last-OV-TR, in % of opening
The warning condition occurs when a variable reaches a critical value and/or a maintenance action is required, but the actuator control functions
are still available. The alarm condition occurs when a variable is out of the acceptable range and the actuator control functions are not available.
Thealarm and warning lists only contain the present alarms and warnings. When the fault condition disappears, the corresponding alarm or
warning disappears from the list. A reset routine is provided to clear the type of alarm/warning that are memorized (overtorque, jammed valve, etc.).
The following drawing shows the use of the OPEN/YES, CLOSE/NO and STOP push buttons in function of the local selector position.