EasyManua.ls Logo

BIFFI EFS2000v4 - Page 42

BIFFI EFS2000v4
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
BIFFI FAIL SAFE ELECTRIC ACTUATORS, MODEL EFS2000V4
InstructIon and operatIng Manual
13.3.5 Clear recent data log
The clear recent data log routine allows to
clear the counters of the recent operation log.
This command does not affect the content of
the ‘general operation log’. The date of the
‘clear recent data log’ is memorized and can be
viewed in the maintenance date routine of the
view menu.
Clear procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP within
20 sec (see chapter ‘Local controls, entering
the set-up mode’). Select the language
and enter the password according to the
instructions (see ‘Entering the set-up mode’).
When the message displayed is ‘SET-UP
MODE OK?’ press YES. Press NO to scroll
through the list of available menus and then
press YES to select the Maintenance menu.
• Press NO to scroll through the list of available
routines and then press YES to select clear
recent data log.
• Press YES
• Press YES to clear or press NO to exit.
13.3.6 Set maintenance date
The maintenance date routine allows the
following operations:
• To set the last maintenance date
• To set the next maintenance date
• To set the start-up date
Configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP within
20 sec (see chapter ‘Local controls, entering
the set-up mode’). Select the language
and enter the password according to the
instructions (see ‘Entering the set-up mode’).
13.3.7 Set data logger
The ‘data logger’ routine allows to set the data logger parameters (see View routines,
Maintenance, Data Logger). To start the data logger the following data should be set:
Logger mode: Recorder, event, off, T-recorder
Sampling time: From 1 to 3600 secs (the sampling time is only used in recorder mode)
Memory mode: Stop when memory is full, continuous = stop after overwriting 5000 times (event)
and 10000 times (recorder/T-recorder) the memory
Logger mode: Recorder, event, off , T-recorder
Sampling time: From 1 to 3600 secs (the sampling time is only used in recorder mode)
Memory mode: Stop when memory is full, continuous = stop after overwriting 5000 times (event)
and 10000 times (recorder/T-recorder) the memory
Start date: Date when the logger starts
Start time: Time when the logger starts
Start date: Date when the logger starts
Start time: Time when the logger starts
When the message displayed is ‘SET-UP
MODE OK?’ press YES. Press NO to scroll
through the list of available menus and then
press YES to select the Maintenance menu.
• Press NO to scroll through the list of
available routines and press YES to select
maintenance date.
• Press YES to set the last maintenance date.
Press NO to skip to ‘next maintenance date’.
Last maintenance date
• Press YES if the date is correct, press NO to
change it.
• Enter day, month, and year. Press NO to
scroll through the list of available values,
press YES to select.
• Press YES if the date is correct.
Next maintenance date
• Press YES if the date is correct, press NO to
change it.
• Enter day, month, and year. Press NO to
scroll the list of available values, press YES
to select.
• Press YES if the date is correct.
Start-up date
• Press YES if the date is correct, press NO to
change it.
• Enter day, month, and year. Press NO to
scroll through the list of available values,
press YES to select.
• Press YES if the date is correct.