KB 23 / KB 23-UL (E3.1) 02/2019 page 41/87
Press key
Display 1 shows
0000
(no function)
Display 2 shows Decimal: XXX.X
(setting of decimal point position)
(actual setting: XXX.X)
Select decimal point position using arrow
keys
Decimal point position XXX.X or XXXX. is
shown in display 2.
Press key
Display 1 shows
0000
(no function)
Display 2 shows Buzzer : Active
(setting of the alarm buzzer)
(actual setting: „Active“)
Select between “Active” and “Inactiv” using
arrow keys
Setting is shown in display 2.
Press key
Display 1 shows
0000
(no function)
Display 2 shows Language : English
(selection of controller language)
(actual setting: English)
Select between languages German, English,
and French using arrow keys
Setting is shown in display 2.
Press key
Display 1 shows
e.g. 0004
(chamber operating hours)
Display 2 shows Oper.hs 0004:28
(operating hours up to now hhhh:mm)
(actually displayed: 4 hs 28 min)
Press key
Display 1 shows
e.g. 9999
(actual setting: 9999 hs)
Display 2 shows Op.limit 9999:00
(maximum number of operating hours
hhhh:mm (actual setting: 9999 hs)
Set value using arrow keys
Setting is shown in both displays.
Press key
Display 1 shows
0000
(no function)
Display 2 shows Op.back : No
(reset counter of operating hours ?)
(actual setting: No)
Select between “Yes” and “No” using arrow
keys
Setting is shown in display 2.
Press key
Display 1 shows
0000
(no function)
Display 2 shows Protocol: MODBUS
(Selection of interface mode)
(actual setting: Modbus)
Select between protocols “MODBUS” and
“Printer” using arrow keys
Setting is shown in display 2.
Press key