EasyManua.ls Logo

Bitzer KT-230-2 - Configuring the CM-RC-01 with the BEST SOFTWARE; Setting the Current Time; Selecting the Motor Start Function; Activating Peripheral Devices

Bitzer KT-230-2
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KT-230-228
• Select UPDATE FIRMWARE (1) and BROWSE… (2) (see
figure 13, page 28).
• Search folder (...\BEST\Firmware\CM-RC-01) for
new firmware.
• Start firmware update and wait until the successful
update is confirmed. Confirm with OK (3).
Fig.13: Updating the firmware
• Selection of BLUETOOTH
A firmware update is not possible via the Bluetooth
interface.
All available devices are listed.
• Select compressor.
• Click on the CONNECT button.
• Enter the Bluetooth password. Factory setting from
firmware version 2.6.58.00:"8670", previous ver-
sions:"2".
The compressor module is now connected to the PC or
mobile device.
10.2 Configuring the CM-RC-01 with the BEST
SOFTWARE
The compressor module CM-RC-01 is preconfigured
for use with the respective compressor as delivered.
Check all settings in the CONFIGURATION menu and
change them if necessary. Check these entries in par-
ticular:
• MOTOR STARTER FUNCTION because of the time switch-
ing of the motor contactors, see chapter Switching
times of the motor contactors at compressor start,
page 13.
• REFRIGERANT
• DATE
• TIME
10.2.1 Setting the current time
Check the programmed date and time using the BEST
SOFTWARE:
• Check the CONFIGURATION menu, the MAIN SETUP win-
dow and the DATE and TIME lines.
• Correct the data if necessary.
10.2.2 Selecting the motor start function
The compressor module switches the motor contactors
on and off. With the BEST SOFTWARE, you can
choose between star-delta, part-winding or direct on-
line start and frequency inverter operation.
Adjust in the BEST SOFTWARE:
• Set the appropriate motor start function in menu
CONFIGURATION, window MOTOR STARTER FUNCTION.
In any case, the compressor motor starts 1s after the
start signal of the superior controller.
10.2.3 Activating peripheral devices
These functions must be activated with the
BEST SOFTWARE after installation and electrical con-
nection of the respective components:
• Application-limit monitoring
• High- and low-pressure transmitters (B6 and B7)
• Additional fan (M2)
• RI System (RI injection valve Y5)
• Open the BEST SOFTWARE.
• In the menu CONFIGURATION, in the column USER SET-
TING, click on each connected peripheral device and
enter YES in each case.
10.2.4 Activating application limits monitoring
➙ Prerequisite: High- and low-pressure transmitters
must be installed.
• Set the refrigerant in the BEST SOFTWARE: in the
menu MAIN SETUP, window REFRIGERANT, select the re-
frigerant used.
• In the menu MAIN SETUP, window PROTECTION FUNC-
TIONS, row ENABLE APPLICATION ENVELOPE PROTECTION in
the column USER SETTING, enter YES.

Table of Contents