17.5.2 Extended Current Controller
For some machines it might be necessary, that for different current ranges different
Amplification factors must be set up.
The following classification applies:
Current < Current below P. 777 is in effect 776
Amplification low Current 777
Current above P. 700 is in effect 775 > Current
> Current below P. 700 is in effect 757 Amplification 700
Current > Current above P. 759 is in effect 758 Amplification high Cur-
rent
759
By default, the parameters are pre-assigned so that the parameters are not active
and only the basic parameters are active.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
757 Current below P. 700 is in effect 0.00 o * I
FIN
o * I
FIN
758 Current above P. 759 is in effect 0.00 o * I
FIN
o * I
FIN
759 Amplification high Current 0.00 8.00 0.00
775
Current above P. 700 is in effect
0.00
o * I
FIN
0.00
776
Current below P. 777 is in effect
0.00
o * I
FIN
0.00
777
Amplification low Current
0.00
8.00
0.00
I
FIN
= Nominal Output current of Frequency inverter
o: Overload capability of Frequency inverter
The motor autotuning changes the parameters.
17.5.3 Torque Controller
The torque-controlled configurations 230, 430, 530 and 630 can be used for sensor-
less torque control alternative to the speed control. The torque control is usable
above the Frequency Limit 624. Below the Frequency Limit 624 the current impres-
sion is active with the current reference frequency as reference value. In this case
the torque is not controlled, but results depending on the load and the Starting cur-
rent
623. To achieve a starting in torque control
, the reference frequency should be
set higher than Frequency Limit 624. This is guaranteed in example by setting Min-
imum frequency
418 > Frequency Limit 624.
f <
Frequency Limit 624: Current impression
f
Frequency Limit 624: Direct Torque Control
The Frequency Limit 624 is set automatically during the motor setup.
06/13 Operating Instructions ACU 229

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI ACTIVE Cube ACU 401-25 and is the answer not in the manual?

BONFIGLIOLI ACTIVE Cube ACU 401-25 Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelACTIVE Cube ACU 401-25
CategoryInverter
LanguageEnglish

Related product manuals