Front panel AC-UPS GD 128x64
OMX76014 Rev. A
25
5.1 DEFINITION OF THE OPERATING STATUS
Status
S1
RECTIFIER ON
Description
The rectifier bridge is on.
Operating
condition
The rectifier is on.
Status
S2
RECTIFIER OK
Description
The rectifier is working properly.
Operating
condition
The rectifier has no system alarm on (e.g. ROCB open A14, etc.).
Status
S3
FLOATING CHARGE
Description
The rectifier (battery charger) works in charge floating.
Operating
condition
The output direct voltage is at the floating charge level.
Status
S4
BOOST CHARGE
Description
The rectifier (battery charger) executes a boost charge cycle.
Operating
condition
The output direct voltage is at the boost charge level.
Status
S5
MANUAL CHARGE
Description
The rectifier (battery charger) is working in manual mode.
Operating
condition
The output direct voltage is adjustable using the manual charge
potentiometer.
Status
S6
BATTERY TEST
Description
The rectifier (battery charger) is executing a battery test.
Operating
condition
The output direct voltage is different based on the test request.
Status
S7
FLOATING IMPOSITION
Description
Forced setting of the floating charge.
Operating
condition
The output direct voltage is set on the floating charge.
Status
S8
MANUAL CHARGE INHIBITION
Description
The manual charge function is uninhibited.
Operating
condition
The rectifier does not allow activation of the manual charge.
Status
S9
MASTER
Description
In parallel configuration the unit is the MASTER.
Operating
condition
The MASTER status is enabled if connected to another rectifier.