Front panel AC-UPS GD 128x64
28 OMX76014 Rev. A
5.2 ALARMS: TROUBLESHOOTING
The voltage or frequency of the input line are out of tolerance.
Possible
causes
Mains instability or fault.
Wrong rotation.
Solutions
1. Check connections to the electrical mains.
2. Check stability of the mains voltage.
3. If the alarm persists, contact our technical support service.
Rectifier bridge input fuses fault.
Possible
causes
Output short circuit.
Overload.
Solutions
1. Contact our technical support service.
RECTIFIER HIGH TEMPERATURE
Description The temperature of the rectifier heat sink exceeds the higher
Possible
causes
Cooling system failure.
Rectifier bridge irregular conduit.
Solutions
1. Check the conduit conditions on all three input phases.
2. Check the fans and the cooling system are working properly.
3. If the alarm persists, contact our technical support service.
Description The current sensor has detected rectifier output overload. If the
alarm persists, thermal image protection is activated (alarm A20), if
Possible
Output overload.
Solutions
1. Check the charges connected in output of the rectifier.
2. Contact our technical support service.
MAXIMUM RECTIFIER VOLTAGE
Description The direct voltage measured has surpassed the higher threshold
Possible
Circuit fault of control or measurement.
Solutions
1. Check the actual value of the direct voltage measured and
reset the device.
2. If the alarm persists, contact our technical support service.