Front panel AC-UPS GD 128x64
32 OMX76014 Rev. A
Possible
causes
Emergency level setting.
Buffer charge setting.
Disabled manual charge.
Rectifier off.
Solutions
1. Check which alarms are present and execute the indicated
procedures.
2. If the alarm persists, contact our technical support service.
Inverse polarity detected on the connection terminals of the battery.
Possible
Wrong connection of the battery cables
Solutions
1. Check the battery connection.
2. If the alarm persists, contact our technical support service.
The battery has not passed the automatic test.
Possible
causes
Battery disconnected.
The battery is not working properly.
Solutions
1. Check the battery status.
2. If the alarm persists, contact our technical support service.
Switch Q11 open (only in configurations using Q11).
Possible
Battery Q11 open.
Solutions
1. Check the switch auxiliary contact is working.
2.
If the alarm persists, contact our technical support service.
The rectifier parallel CAN-BUS serial communication is not working.
Possible
causes
Wrong setting of the unit position.
The CAN-BUS cable is disconnected.
Solutions
1. Check the settings and the cable.
2. If the alarm persists, contact our technical support service.