Front panel AC-UPS GD 128x64
OMX76014 Rev. A
33
Description In parallel configuration of the rectifier, the system cannot manage
to sub-divide the load even if the conditions are present.
Possible
causes
Current sensor disconnected.
The parallel switch contacts are interrupted.
Solutions
1. Check the sensors and the auxiliary contact.
2. If the alarm persists, contact our technical support service.
The SBCB bypass switch is open.
Possible
causes
SBCB bypass switch open.
Switch auxiliary contact faulty.
Solutions
1. Check the switch auxiliary contact is working.
2. If the alarm persists, contact our technical support service.
The ELCB emergency line switch is open.
Possible
causes
ELCB emergency line switch open
Switch auxiliary contact faulty.
Solutions
1. Check the switch auxiliary contact is working.
2. If the alarm persists, contact our technical support service.
Rectifier manually switched off.
Possible
causes
Rectifier switched off from panel.
Rectifier switched off from front switch.
Rectifier switched off from specific digital contact.
Solutions
1. Check the points in the "Possible causes".
2. If the alarm persists, contact our technical support service.
RECTIFIER CONTROL ERROR LOOP
Possible
Circuit fault of control or measurement.
Solutions
1. Check the connections of the measurements and the control
circuit.
2. If the alarm persists, contact our technical support service.