Front panel AC-UPS GD 128x64
38 OMX76014 Rev. A
At least one of the system valves is not working correctly
Possible
causes
Loss of fan power
Fans fault
Solutions
1. Check fans power supply
2. Replace faulty fan
3. If the alarm persists, contact our technical support service.
The inverter parallel CAN-BUS serial communication is not working
Possible
causes
Wrong setting of the unit position
Cable interrupted
Solutions
1. Check the settings and the cable
2. If the alarm persists, contact our technical support service.
CAN INVERTER DISCONNECTED
The inverter parallel cable is not connected
Possible
Parallel cable not connected properly
Solutions
1. Check the cable connection is correct
2. If the alarm persists, contact our technical support service.
Description The parallel inverter number is not sufficient to guarantee the
minimum redundancy necessary for the system
Possible
One or more parallel systems are faulty or off
Solutions
1. Reset the faulty or off systems
2. If the alarm persists, contact our technical support service.
An error occurred inside the control logic
Possible
Internal malfunctions
Solutions
1. Contact our technical support service.