EasyManua.ls Logo

Bosch AMAX panel 2000 - Bypassing Faults and Tamper Conditions (Except Zone Tampers); Change Individual Code; Duress Alarm; Enable; Disable the Installers Code

Bosch AMAX panel 2000
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AMAX panel 2000 / AMAX panel 2000 EN User Guide | en 27
Bosch Sicherheitssysteme GmbH Installation Manual F.01U.241.127 | V4 | 2011.12
4.7.2 Bypassing Faults and Tamper conditions (Except Zone Tampers)
Bypassing Faults and Tamper conditions, one or more faults and tamper conditions are
disabled for one arming cycle. After bypassing a Fault or Tamper condition, you can arm the
system even when a Fault or Tamper condition exists.
How to bypass faults and tamper conditions
1. Enter your user code + [97] and press [#].
Two beeps sound.
4.8 Enable / Disable the installers code
This function allows user code holder to enable or disable the installer code.
Installer can only perform actions when he is enabled by a user.
1. Enter your user code + [98] and press [#] to enable the function.
Two beeps sound.
2. Enter your user code + [98] and press [*] to disable the function.
Two beeps sound.
4.9 Change individual code
This function allows user to change their individual code.
How to change the code
1. Enter your code and press [99] [#].
Two beeps sound and the STAY and AWAY indicators flash, and your user number is
shown on the keypad.
2. Enter the new code and press [#].
Two beeps sound and the STAY and AWAY indicators are extinguished.
4.10 Keypad alarm operation commands
4.10.1 Duress alarm
A keypad duress alarm is used as a silent holdup alarm when 0 is added to the end of a valid
Code used to disarm the system ( [code] + [0] + [#] ).
A duress alarm is useful only if your system reports to a monitoring station. Domestic
reporting cannot define the type of alarm that occurred.
4.10.2 Keypad panic alarm
If you simultaneously press and hold [1] and [3] or simultaneously press and hold [*] and [#],
a silent emergency alarm will be transmitted. Please contact your installer to enable/disable
the keypad emergency alarm functionality.
Simultaneous pressing and holding the wireless remote control key arming and disarming key
can also transmit a wireless emergency alarm.
4.10.3 Keypad fire alarm
If you simultaneously press and hold [4] and [6], a silent keypad fire alarm will be transmitted.
Please contact your installer to enable/disable the fire alarm functionality.
NOTICE!
This function is automatically terminated if you do not press a button within 240 seconds or if
you press [#]. One long beep indicates that the code already exists or that you entered an
incorrect user number.