80 en | Programming sheets AMAX panel 2000 / AMAX panel 2000 EN
F.01U.241.127 | V4 | 2011.12 Installation Manual Bosch Sicherheitssysteme GmbH
10.2.2 Test Report Time Interval Setting
10.3 System Functions Programming
10.3.1 Ring Count
10.3.2 Remote Programming/Control
10.3.3 Call back Telephone Number
10.3.4 Exit Time
10.3.5 Entry Time
5 Report to Receiver 1,2,3,4
6 Report to destination 1 (2,3,4 backup)
7 Report to destination 1 (2 backup) and destination 3 (4 backup)
Zone Status Reporting Options
NOTICE!
The system sends no report when programmed to report to the receiver as Option 0.
Location 145-150
Default
145-146=timer test report(1-99 hours)0=don’t send timer
test report
24
EN=1-24
147-148=Report time: Hours=0-23(else=don’t send real time
test report)
99
149-150=Report time: minutes=0~59(else=don’t send real
time test report)
99
Location 152 Location Default
0=Panel does not answer
1–15= Number of rings until panel answers
152 0
Location 153 Location Default
0=Disable 1=Enable 153 1
Location 154-169 Location Default
15 = telephone termination 154-169 15
Location 170-172 Location Default
000-255 seconds 170-172 045
Location 173-175 Location Default
000-255 seconds 173-175 045
EN=45