The following conditions apply for an RS-485 bus system:
A bus system consists of a bus line and/or one or more
branch lines.
Cable lengths exceeding 100 m (300 ft) must be installed
as bus lines.
Branch lines are branching connections from a bus line.
Peripheral devices are AMC2 which are connected to the
host computer.
Maximum cable length of a bus line must not exceed
1200 m (4000ft).
The cable length of branch lines must not exceed 100m
(330ft).
Any bus line conductor connects up to eight AMC2. Do not
exceed the maximum number of devices.
To use RS-485 mode at the AMC2-4W , connect the data cables
to the pluggable screw connector of the RS-485 host interface.
The setting of the AMC2-4W must correspond with the settings
of the RS-232 / RS-485 converter.
Figure 4.10: RS-485 host interface