DIL Switches
1 2 3 4
None OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
Table 4.1: Setting the address via the DIL switch
Instructions for DIL switch 5
Set SDEB (= DIL switch 5 to ON) in the following cases
Ethernet host connection
RS-485 host connection, provided only one AMC2 is
connected on the bus
Set BPA (= DIL switch 5 to OFF) in the case of an
RS-485 host connection with more than one and maximum
eight AMC2s per bus
Notice!
Changing the type of the host connection requires a reset of
the AMC2 - see Resetting the Software, page 52.