14 en | System Overview AVENAR detector 4000
2023-06 | 07 | F.01U.283.550
User manual
Bosch Sicherheitssysteme GmbH
MH400 Detector Heating Element
The MH400 Detector Heating Element is required if the
detector is used in an environment where water
condensation can occur, such as in a warehouse that must
frequently be opened briefly for delivery vehicles.
The detector heating element is connected to the + V/0V
terminals in the detector base.
Operating voltage: 24VDC
Resistance: 1kΩ
Maximum power dissipation: 3W.
The heating is supplied with power either by the fed-
through supply voltage via the central unit or by a separate
power pack.
With supply via the central unit, the number of detector
heating elements depends on the cable diameter and line
length used.