AVENAR detector 4000 Programming | en 19
Bosch Sicherheitssysteme GmbH
User manual
2023-06 | 07 | F.01U.283.550
4.3 FAP‑425‑DO‑R / FAP‑425‑O‑R / FAP‑425‑O
Notice!
The default setting of FAP-425-DO-R, FAP-425-O-R and FAP-425-O in FSP-5000-RPS is
Medium.
Installation location Sensitivity
Office after hours High
Hotel room/smoker room Low
Office day mode Medium
Server room High
Production location Low
Warehouse without combustion-engine traffic High
Conference room/waiting room/exhibition hall Low
School/kindergarten Medium
Theater/concert hall Medium
Warehouse with combustion-engine traffic Low