AVENAR detector 4000 Basic installation and configuration notes | en 15
Bosch Sicherheitssysteme GmbH
User manual
2023-06 | 07 | F.01U.283.550
3 Basic installation and configuration notes
– Multi-sensor fire detectors must be planned in line with the guidelines for optical
detectors until a guideline for their planning is developed in collaboration with the VdS
(see also DIN VDE0833 Part2 and VDS2095):
– Maximum monitoring area 120m
2.
– Maximum installation height 16m.
– If occasional switch-off of the optical sensor is required, the planning must occur
according to the guidelines for heat detectors (see DIN VDE 0833 Part 2 and VDS 2095):
– Maximum monitoring area 40m
2.
– Maximum installation height 7.5m.
– Maximum permissible air speed: 20m/s.
– FAH-425-T-R detectors must be configured according to category A1R when planning fire
barriers conforming to DIBt.
Notice!
AVENAR detector 4000 Automatic Fire Detectors are not designed for exterior use.
Notice!
Planning must take the anticipated total current and line resistance into account to ensure
each detector has an operating voltage of at least 15VDC.
Notice!
Operating temperature
When using AVENAR detector 4000 in combination with AVENAR all-in-one 4000 consider the
operation temperature of -10 to +55°C.