18 en | Programming AVENAR detector 4000
2023-06 | 07 | F.01U.283.550
User manual
Bosch Sicherheitssysteme GmbH
4.2 FAP‑425‑DOT‑R / FAP‑425‑OT‑R / FAP‑425‑OT
i
Notice!
The default setting of FAP-425-DOT-R, FAP-425-OT-R and FAP-425-OT in FSP-5000-RPS is
Office day mode.
Installation location Detector
type
Sensitivity Standard
Temperature (T) Optical (O)
Office after hours O, T
max
, T
diff
High (A2R) High EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
Hotel room/smoker room O, T
max
, T
diff
High (A2R) Low EN 54-5, EN 54-7
Office day mode
= default setting
O, T
max
, T
diff
Low (BR) Medium EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
Server room O, T
max
, T
diff
High (A2R) High EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
Production location O, T
max
, T
diff
Low (BR) Low EN 54-5, EN 54-7
Garage
FAP-425-OT-R, FAP-425-OT
FAP-425-DOT-R
T
max
, T
diff
O, T
max
, T
diff
High (A2R)
High (A2R)
-
Low
EN 54-5
EN 54-5, EN 54-7
Warehouse without combustion-engine
traffic
O, T
max
, T
diff
Low (BR) High EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
Conference room/waiting room/exhibition
hall
O, T
max
, T
diff
High (A2R) Low EN 54-5, EN 54-7
Kitchen/casino/restaurant T
max
Low (BS) - EN 54-5
Warehouse with combustion-engine traffic O, T
max
, T
diff
Low (BR) Low EN 54-5, EN 54-7
Thermal sensor: fixed and rate-of-rise
temperature
T
max
, T
diff
High (A2R) - EN 54-5
Optical sensor O - Low -
Thermal sensor: fixed temperature T
max
High (A2S) - EN 54-5
School/kindergarten O, T
max
, T
diff
High (A2R) Medium EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
Theater/concert hall O, T
max
, T
diff
High (A2R) Medium EN 54-5, EN 54-7,
EN 54-29 (FAP-425-
DOT-R only)
O = optical sensor (dual-optical in FAP-425-DOT-R detectors), CO = chemical sensor (for CO gas)
T
max
= thermal maximum unit, T
diff
= thermal differential unit