AVENAR detector 4000 Programming | en 17
Bosch Sicherheitssysteme GmbH
User manual
2023-06 | 07 | F.01U.283.550
Installation location Detector type Sensitivity Standard
Temperature
(T)
Optical (O) Chemical (C)
Warehouse without
combustion-engine traffic
O, T
max
, T
diff
, C Low (BR) High High EN 54-5, EN 54-7,
EN 54-29
Conference room/waiting
room/exhibition hall
O, T
max
, T
diff
, C High (A2R) Low* Medium EN 54-5, EN 54-7
Kitchen/casino/restaurant O, T
max
, C Low (BS) Low* Low EN 54-5, EN 54-7
Warehouse with
combustion-engine traffic
O, T
max
, T
diff
, C Low (BR) Low* Low EN 54-5, EN 54-7
Thermal sensor: fixed and
rate-of-rise temperature
T
max
, T
diff
High (A2R) - - EN 54-5
Optical sensor O - Low - -
Thermal sensor: fixed
temperature
T
max
High (A2S) - - EN 54-5
Optical and CO sensor O, C - Low High -
School/kindergarten O, T
max
, T
diff
, C High (A2R) Medium High EN 54-5, EN 54-7,
EN 54-29
Theater/concert hall O, T
max
, T
diff
, C High (A2R) Medium High EN 54-5, EN 54-7,
EN 54-29
Optical + thermal + CO
sensor: high sensitivity**
O, T
max
, T
diff
, C High High High VdS 6019
Optical + thermal + CO
sensor: low sensitivity**
O, T
max
, T
diff
, C Low Medium High VdS 6019
Thermal and CO sensor*** T
max
, T
diff
, C Low - High VdS 6018
CO sensor*** C - - High VdS 6017
O = optical sensor, T
max
= thermal maximum unit, T
diff
= thermal differential unit, C = chemical sensor
* If optical sensor sensitivity is low, the detector will only trigger if smoke as well as an increase in CO
concentration or temperature is detected.
** Suppression of single fire phenomena, only available for FAP-425-DOTCO-R
*** only available for FAP-425-DOTCO-R