4 Programming
Programming occurs via a PC or laptop connected to the fire panel with FSP-5000-RPS
(Remote Programming System) for panels with LSN improved version line technology
AVENAR detector 4000 is programmed by entering the area of operation. The selection of the
area of operation determines the optimum characteristic field for fire and disturbance variable
evaluation.
The operating mode can be changed for FAP-425-OT-R|FAP-425-OT, as well as for FAP-425-
DOTC-R|FAP-425-DOTCO-R and FAP-425-DOT-R, i.e. individual sensors can be switched off:
Switch to optical (O sensor sensitivity = low, T sensor = switched off)
Switch to thermal differential (T sensor sensitivity = A2R, O sensor = switched off)
Switch to thermal maximum (T sensor sensitivity = A2S, O sensor = switched off).
In the case of the purely optical FAP-425-O-R|FAP-425-O and FAP-425-DO-R detectors, the
sensitivity of the optical sensor can be set to three levels. Depending on the operating
location, the optical sensor in the detector is thus adjusted to the environmental conditions.
i
Notice!
For fire detection, the purely optical detector also evaluates the time behavior of the fire
characteristics, which differs significantly from the time behavior of disturbance variables and
that occurring during a detector test
As a result, there are also different trigger times when testing with a test aerosol outside of
Walk test operation (10s to max 60s), depending on the selected sensitivity adjustment.
FAH-425-T-R is programmed by taking into account the ambient temperature, the installation
height and the category as per EN54 Part5.
Programming of the optical, thermal, and chemical sensors and the linking of all sensors via
algorithms significantly increases the detection ability and security against false alarms.
4.1 FAP-425-DOTC-R and FAP-425-DOTCO-R
i
Notice!
The default setting of FAP-425-DOTC-R and FAP-425-DOTCO-R in FSP-5000-RPS is Hotel
room/smoker room.
Installation location Detector type Sensitivity Standard
Temperature
(T)
Optical (O) Chemical (C)
Office after hours O, T
max
, T
diff
, C High (A2R) High High EN 54-5, EN 54-7,
EN 54-29
Hotel room/smoker room
= default setting
O, T
max
, T
diff
, C High (A2R) Low* Low EN 54-5, EN 54-7
Office day mode O, T
max
, T
diff
, C Low (BR) Medium High EN 54-5, EN 54-7,
EN 54-29
Server room O, T
max
, T
diff
, C High (A2R) High High EN 54-5, EN 54-7,
EN 54-29
Production location O, T
max
, T
diff
, C Low (BR) Low* Medium EN 54-5, EN 54-7
Garage O, T
max
, T
diff
, C High (A2R) Low* Low EN 54-5, EN 54-7