AVENAR detector 4000 Connection | en 27
Bosch Sicherheitssysteme GmbH
User manual
2023-06 | 07 | F.01U.283.550
FAA‑420‑RI‑ROW FAA‑420‑RI‑DIN
Operating mode 3:
11 to 33 V DC
Current feed 3 to 30mA Operating mode 1:
3 to 30mA
Operating mode 2:
11 to 14 mA
Operating mode 3:
3mA
Permissible wire gauge 0,4-1,3mm 0,6-1,0 mm
Display medium 1LED 1LED
Dimensions 85x 85x28mm 85x85x35mm
Weight 45g 65g
FAA‑420‑RI‑DIN
!
Warning!
Malfunction and Damage
Note the maximum permitted current supply respectively the input voltage range of the
functional modes.
4 Wire the remote indicator as shown.
Mode Terminal connection Alarm condition
1
+
The remote indicator shows steady red light.
2
+
The remote indicator shows steady red light.
3
+
The remote indicator shows flashing red light.
Operate in mode 1 and 3 only, when connected to LSN detectors.