test emits a brief tone, and for 60 seconds the display indicates
that the point was tested. The tone and display verify that each
detection device is working properly. Keypads within the area’s
scope from which you did not initiate the walk test show Walk
test in progress during the testing.
Notice!
Fire walk test includes gas
When you perform a Fire walk test, the security system
tests any 24-hour points that are not invisible, including
gas points.
Performing a walk test:
1. Open the Main menu.
2. Use [NEXT] to go to the Actions menu option, and press
[ENTER], or simply press [3].
3. Use [NEXT] to go to the Test menu option, and press
[ENTER], or simply press [3].
4. Press [1] or [ENTER] to open the Walk Test menu.
5. Enter your passcode and press [ENTER].
6. Use [NEXT] to go to the desired walk test, and press
[ENTER], or simply press the number key for the desired walk
test: [1] for Fire, [2] for Intrusion, [3] for Service, or [4] for
Invisible.
7. Press [ENTER] to view the points.
156 en | B92x/B91x Actions menu Control Panels
2015.01 | 02 | F.01U.307.371 Bosch Security Systems, Inc.