EasyManua.ls Logo

Bosch FW 200 - Safety Instructions

Bosch FW 200
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 643 256 (2010/05)
8 | Explanation of symbols and safety information US/CA
1.2 Safety instructions
B To ensure proper function, follow these
instructions.
B Install and start up the boiler and all
accessories according to the associated
instructions.
B Only have this accessory installed by a trained
and certified installer.
B Use this accessory exclusively in conjunction
with the controllers and heating appliances
listed. Follow the connection diagram!
B Never connect this accessory to 120 VAC line
voltage.
B Prior to mounting this accessory:
Isolate the boiler from the power supply
(120 VAC) using the emergency shut-off
switch or the heating system circuit breaker.
B Electrical components must be installed by a
trained electrician and the installation must
meet the National Electric Code as well as all
applicable local codes and regulations.
B Provide a dedicated circuit breaker for the
boiler and heating system rated at least 15 A.
B All line voltage wiring must use at least
AWG14 size cables.
B In case of wall mounting: never mount this
accessory in wet areas.
B Instruct customers about the functions and
operation of this accessory.
B Risk of scalding during thermal disinfection:
Due to DHW temperatures occurring in excess
of 140 °F (60 °C), Bosch strongly advises to
install a DHW thermostatic mixing valve.
B When there is a risk of frost, leave the boiler
switched on and follow the frost protection
information.

Table of Contents