EasyManua.ls Logo

Bosch Greensource CDi Series - Page 49

Bosch Greensource CDi Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting | 49SM Series Heat Pump
8733942411 (2017/06)Revised 07-17
SM070 Full Load
COOLING HEATING
Entering
Water
°F
Water
flow
GPM
Discharge
Pressure
(PSIG)
Suction
Pressure
(PSIG)
Subcooling
°F
Superheat
°F
Water
Temp
Rise °F
Air
Temp
Drop °F
Entering
Water
°F
Water
flow
GPM
Discharge
Pressure
(PSIG)
Suction
Pressure
(PSIG)
Subcooling
°F
Superheat
°F
Water
Temp
Drop °F
Air
Temp
Rise °F
30
9 170 - 174 135 - 141 20 - 22 8 - 9 16 - 20 20 - 24
20
9 265 - 324 57 - 70 8 - 16 8 - 22 7 - 10 18 - 26
15 151 - 154 134 - 140 13 - 15 7 - 9 10 - 12 20 - 25 12 269 - 328 60 - 73 7 - 14 8 - 21 6 - 8 18 - 27
18 147 - 150 134 - 139 12 - 13 8 - 9 8 - 10 20 - 25 18 272 - 332 63 - 77 6 - 12 8 - 21 4 - 6 19 - 28
40
9 178 - 218 125 - 153 11 - 31 5 - 14 11 - 28 17 - 26
30
9 279 - 340 69 - 84 9 - 17 8 - 20 8 - 12 20 - 30
15 160 - 196 124 - 152 8 - 20 5 - 14 6 - 17 18 - 26 12 282 - 345 72 - 88 8 - 15 8 - 20 6 - 9 20 - 30
18 155 - 190 124 - 152 7 - 17 5 - 14 5 - 14 18 - 27 18 287 - 351 76 - 93 6 - 13 7 - 20 5 - 7 21 - 32
50
9 205 - 251 127 - 156 14 - 23 5 - 14 14 - 20 17 - 25
40
9 293 - 358 81 - 99 10 - 18 7 - 19 9 - 14 22 - 33
15 185 - 226 126 - 154 9 - 16 5 - 14 8 - 12 17 - 26 12 297 - 364 86 - 105 9 - 16 7 - 19 7 - 11 23 - 35
18 180 - 220 125 - 153 8 - 15 5 - 14 7 - 11 17 - 26 18 303 - 370 91 - 111 7 - 14 7 - 19 5 - 8 24 - 36
60
9 234 - 286 127 - 156 13 - 22 5 - 14 13 - 20 16 - 25
50
9 308 - 377 95 - 117 12 - 20 7 - 19 10 - 16 25 - 37
15 213 - 261 126 - 154 8 - 15 5 - 15 8 - 12 17 - 25 12 314 - 384 101 - 124 10 - 17 7 - 18 8 - 12 26 - 39
18 208 - 255 125 - 153 7 - 14 5 - 14 7 - 10 17 - 25 18 321 - 393 108 - 132 8 - 15 7 - 18 6 - 9 27 - 40
70
9 267 - 327 129 - 157 12 - 20 5 - 13 13 - 19 16 - 24
60
9 325 - 397 111 - 136 13 - 21 7 - 18 12 - 18 28 - 41
15 245 - 299 127 - 156 8 - 14 6 - 15 8 - 12 16 - 25 12 332 - 406 118 - 145 11 - 18 6 - 17 9 - 14 29 - 43
18 239 - 293 127 - 156 6 - 13 5 - 15 7 - 10 16 - 25 18 341 - 416 127 - 155 8 - 16 6 - 17 7 - 10 30 - 45
80
9 302 - 369 132 - 161 11 - 19 6 - 15 13 - 19 16 - 24
70
9 343 - 419 128 - 157 14 - 23 6 - 17 13 - 20 30 - 45
15 279 - 341 129 - 158 7 - 13 6 - 17 8 - 12 16 - 24 12 351 - 429 137 - 167 12 - 20 6 - 17 10 - 16 32 - 47
18 275 - 336 129 - 158 6 - 12 5 - 13 6 - 9 16 - 23 18 362 - 442 148 - 180 9 - 16 6 - 17 7 - 11 33 - 50
90
9 341 - 416 132 - 161 10 - 18 6 - 16 12 - 19 15 - 23
80
9 362 - 442 147 - 180 16 - 25 6 - 17 15 - 22 33 - 50
15 318 - 388 130 - 158 6 - 13 6 - 16 7 - 11 16 - 23 12 371 - 454 158 - 193 13 - 21 6 - 17 12 - 17 35 - 52
18 312 - 381 132 - 161 5 - 11 6 - 16 6 - 9 16 - 23 18 384 - 469 171 - 209 10 - 17 6 - 16 8 - 12 36 - 55
100
9 383 - 468 134 - 163 9 - 16 6 - 16 12 - 18 15 - 22
90
9 381 - 466 168 - 205 17 - 26 6 - 16 16 - 24 36 - 54
15 360 - 440 132 - 162 5 - 12 6 - 16 7 - 11 15 - 23
12 393 - 481 181 - 222 14 - 23 6 - 16 13 - 19 38 - 57
18 354 - 433 132 - 161 4 - 10 6 - 16 6 - 9 15 - 23
18 407 - 497 196 - 240 11 - 18 6 - 16 9 - 14 40 - 60
110
9 429 - 524 135 - 165 8 - 15 7 - 18 12 - 18 14 - 22
100
9 402 - 491 191 - 234 18 - 28 6 - 16 18 - 26 39 - 59
15 406 - 496 134 - 164 5 - 11 6 - 16 7 - 11 14 - 22
12 416 - 508 207 - 253 15 - 24 6 - 16 14 - 21 41 - 62
18 400 - 489 134 - 164 4 - 10 6 - 17 6 - 9 15 - 22
18 431 - 527 225 - 275 11 - 19 6 - 16 10 - 15 43 - 65
This chart shows approximate temperatures and pressures for a unit in good normal operation. The values shown are meant as
a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º D.B/67º W.B. Entering
air temperature in cooling, 70º D.B entering air temperature in heating. Heating data at entering fluid temperatures below 50º
assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without
notice.

Table of Contents