ICP-CC408 | Installation Guide | 15.0 System Reporting Information EN | 66
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
15.10 Codepad Fire Report
Location
339 to 340
Location Default
Tens digit 339 7
Units digit 340 14
A Fire Alarm Report (Contact ID Event Code 110) is
sent to the base station receiver when a user presses
[4] and [6] at the same time. A Fire Alarm is audible,
but you can program the alarm as silent by selecting
Option 2 in Location 425 (refer to Section 18.2 System
Options 2 on page 79). A distinct fire sound is emitted
through the horn speaker to indicate this type of
alarm. The fire sound is different than the burglary
sound.
Restore Reports are not sent for this
event.
If Fire Reports are not required, program
Locations 339 and 340 as 0.
15.11 Codepad Medical Report
Location
341 to 342
Location Default
Tens digit 341 7
Units digit 342 13
A Medical Report (Contact ID Event Code 100) is
sent to the base station receiver when a user presses
[7] and [9] at the same time. A Medical Alarm is
audible, but you can program the alarm as silent by
selecting Option 4 in Location 425 (refer to Section
18.2 System Options 2 on page 79).
Restore Reports are not sent for this
event.
If Medical Reports are not required,
program Locations 341 and 342 as 0.
15.12 Codepad Reporting Options
Location
343
0 No Codepad Alarm Reports allowed
1 Report to Receiver 1
2 Report to Receiver 2
4 Report to both Receiver 1 and Receiver 2
8 Report to Receiver 2 only if Receiver 1 fails
This location is set by default to report only to
Receiver 1. You can select whether Codepad Reports
are sent to Receiver 1, Receiver 2, or both, Receiver
2 only when Receiver 1 fails, or there is no reporting
at all.
15.13 System Status – AUX Power
Supply Fail Report
Location
344 to 345
Location Default
Tens digit 344 10
Units digit 345 3
A System Trouble Report (Contact ID Event Code
300) is sent when the AUX Power Supply is blown.
The system reports the event approximately 10 sec
after the
AUX Power Supply fails.
15.14 System Status – AUX Power
Supply Fail Restore Report
Location
346 to 347
Location Default
Tens digit 346 10
Units digit 347 8
A System Trouble Restore Report (Contact ID Event
Code 300) is sent when the failed codepad AUX
Power Supply is restored. The system reports the
event approximately 10 sec after the
AUX Power
Supply
is restored.
15.15 System Status – AC Fail Report
Location
348 to 349
Location Default
Tens digit 348 10
Units digit 349 2
An AC Fail Report (Contact ID Event Code 301) is
sent to the base station receiver when the AC
MAINS supply is disconnected for 2 min. If you do
not want an AC Fail Report to be sent until the AC
MAINS supply is disconnected for 1 hour, select
Option 1 in Location 426 (refer to Section 18.3 System
Options 3 on page 79). If you want to ignore AC Fail,
select Option 2 in Location 426.
If AC Fail Reports are not required,
program Locations 348 and 349 as 0.
15.16 System Status – AC Fail Restore
Report
Location
350 to 351
Location Default
Tens digit 350 10
Units digit 351 7
An AC Fail Restore Report is sent when the AC
MAINS supply is connected continuously for longer
than 2 min.
If AC Fail Restore Reports are not
required, program Locations 350 and 351
as 0.