ICP-CC408 | Installation Guide | 16.0 Programmable Outputs EN | 68
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
A Test Report (Contact ID Event Code 602) is a
specific signal sent to the base station receiver and is
normally used to test the dialing and reporting
functions of the control panel.
When programming Test Report options, specify the
hour and minute of the day the report is required,
and how often to send the report. Test reports are
reported on a daily basis from every day to every
fifteen days. Refer to Section 6.1.1 Set the Number of
Days until the First Test Report on page 29 to set the
first test report.
If Test Reports are not required, program
the repeat interval in Location 366 as 0.
Program the Test Report Time as 24:00
to send reports every 30 min.
Example
If you want to send Test Reports once every seven
days at 11:35 PM, program Locations 360 to 366 as:
[2 3 3 5 7 1 7]
15.22 Test Reporting Dialer Options
Location
367
0 No Codepad Alarm Reports allowed
1 Report to Receiver 1
2 Report to Receiver 2
4 Report to both Receiver 1 and Receiver 2
8 Report to Receiver 2 only if Receiver 1 fails
This location is set by default to report only to
Receiver 1. You can select whether Test Reports are
sent to Receiver 1, Receiver 2, or both, Receiver 2
only when Receiver 1 fails, or there is no reporting at
all.
16.0 Programmable Outputs
The ICP-CC408 Control Panel has four fully-
programmable outputs on the main printed circuit
board and one programmable output that operates
the codepad buzzer. The four outputs are set by
default to operate as horn speaker, fire alarm
verification, strobe, and internal screamer.
Programmable outputs require four parameters to
operate correctly.
Table 57: Output Parameters
Parameter Description
Event Type
The Event Type specifies when an output
is activated. The Output Event Types are
listed in Section 16.2 on page 69. Enter
the code for the Output Event Type into
the two corresponding locations for the
output.
Polarity
Polarity determines whether the output
operates for the duration of the event,
pulses for the duration, operates once
only (one shot), or latches on. The Polarity
options are listed in Table 58 on page
74.
Time Base/
Time
Multiplier
The Time Base and Time Multiplier
parameters determine how long and how
often the output operates. Refer to
Section 16.4 Output Timing on page 75.
Location
368 to 397
Location Default
Output 1 (Default = Horn Speaker)
Event Code 368 1
Event Code 369 14
Polarity 370 0
Time Base 371 0
Time Base Multiplier 372 0
Time Base Multiplier 373 0
Output 2 (Default = Fire Alarm With Verification)
Event Code 374 2
Event Code 375 7
Polarity 376 10
Time Base 377 2
Time Base Multiplier 378 1
Time Base Multiplier 379 3
Strobe Output (Default = Strobe – Reset in 8 hours)
Event Code 380 6
Event Code 381 0
Polarity 382 6
Time Base 383 4
Time Base Multiplier 384 0
Time Base Multiplier 385 8