Page #14 background imageLoading...
Page #14 background image
14 / 50
ctrlX CORE
Voltage supply and current consumption
Bosch Rexroth AG
R911405645, Edition 05
7.2 Voltage supply and current consumption
Table 3: ctrlX CORE X2 and ctrlX CORE X3
Nominal voltage at U
L
DC 24 V SELV/PELV
Maximum permitted voltage range of the supply
voltage U
L
DC 18 V to DC 31.2 V (incl. all tolerances and
ripple)
Max. current consumption of the control from U
L
at
a nominal voltage of 24 V
320 mA
Max. power consumption of the control from U
L
at a
nominal voltage of 24 V
7.68 W
Reverse polarity protection of the supply voltage U
L
Present
Fuse protection U
L
Internal with eFuse, 1.5 A
Overvoltage protection U
L
Available; the protective fuse can trigger in case of
overvoltage
Transient protection U
L
Present, suppressor diodes
Pulse load up to 1,500 W
Voltage dips at current supply interfaces PS1 < 1 ms, evaluation criterion A
Electrical isolation
24 V supply (U
L
/U
L
GND) to the functional earth
DC 707 V
24 V supply voltage (U
L
/U
L
GND) to XF10, XF50,
XF51
DC 1200 V
Table 4: Setup of the voltage supply ctrlX CORE
PLUS
X3
Nominal voltage at U
L
and U
P
DC 24 V SELV/PELV
Maximum permitted voltage range of the supply
voltage U
L
and U
P
DC 18 V to DC 31.2 V (incl. all tolerances and
ripple)
Max. current consumption of the control from U
L
at
a nominal voltage of 24 V
Typ. 400 mA (without I/O modules if U
L
= 24 V),
3.4 A max. (with 3 A for I/O modules if U
L
= 24 V)
Max. power consumption of the control from U
L
at a
nominal voltage of 24 V
Typ. 9.6 W (without I/O modules if U
L
= 24 V),
81.6 W max. (with 3 A for I/O modules if U
L
=24 V)
Current consumption U
P
Typ. 5 mA (without I/O modules), 8 A max., at U
P
=
24 V
Power consumption from U
P
Typ. 0.12 W (without I/O modules), 192 W max.,
at U
P
= 24 V
Reverse polarity protection of the supply voltage U
L
and U
P
Present
Fuse protection U
L
Internal with a protective fuse of 10 A
Fuse protection U
P
No internal fuse protection. The operator has to
provide protection against overload by an external
fuse.
Overvoltage protection U
L
and U
P
Present, fuses can trigger in case of overvoltage.
Transient protection U
L
and U
P
Present, suppressor diodes
Pulse load up to 1,500 W

Table of Contents

Other manuals for Bosch Rexroth ctrlX CORE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Rexroth ctrlX CORE and is the answer not in the manual?

Bosch Rexroth ctrlX CORE Specifications

General IconGeneral
BrandBosch
ModelRexroth ctrlX CORE
CategoryController
LanguageEnglish

Related product manuals