2.3 Supply units
UL ratings and dimensions (XVR)
Description Symbol Unit XVR*-W0048 XVR*-W0072 XVR*-W0100
Listing in accordance with UL
standard
UL 61800-5-1
Listing in accordance with CSA
standard
C22.2 No. 274-17
UL‑Files E328841
Pollution degree 2
Ambient temperature range with
nominal data
T
amax
°C 40
Mass m kg 16 20 27
Device height
1)
H mm 309 340.5
Device depth
2)
T mm 196.5
Device width
3)
B mm 225 250 350
Minimum distance on the top of
the device
4)
d
top
mm 80
Minimum distance on the bottom
of the device
5)
d
bot
mm 80
Horizontal spacing at the device
6)
d
hor
mm
0 (for devices of the ctrlX DRIVE product group in the DC bus
group (central supply))
1.5 (for devices of the ctrlX DRIVE product group outside of the
DC bus group (individual supply))
10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input
7)
U
N3
V 24
Rated control current input
I
N3
A 4
Short circuit current rating SCCR A rms 42000
Rated input voltage, power
8)
U
LN_nenn
V AC 380Y/220V … 500Y/288V
Mains frequency
f
LN
Hz 50 … 60
Rated input current
I
LN
A 76 109 150
Branch circuit protection fuse
9)
Class J Fuse 100A Class J Fuse 125A Class J Fuse 200A
Required wire size in accordance
with UL 508 A (internal wiring);
10)
A
LN
AWG 3 1/0 3/0
Field wiring material (material;
conductor temperature; class)
Cu; 75 °C; 1
Output voltage
U
out
V DC 0 … 750
Output current
I
out
A 64 96 133
ctrlX DRIVE Drive Controllers, Supply Units 17/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG