ctrlX SAFETY "SafeMotion"
Table 37: Motor temperature monitoring, motor holding brake
View Connection Signal name Function
5 MotTemp+ Motor temperature evalu-
ation input
6 MotTemp-
7 +24VBr Output to actuate the
motor holding brake
8 0VBr
Spring terminal (connector) Unit min. max.
Connection cables
Stranded wire
mm
2
0.14 1.5
AWG 26 16
Stripped length mm 8
Current carrying capacity of brake
outputs
A - 1
Time constant of load ms - 50
Number of switching actions at
maximum time constant of load
Wear-free electronic contact
Switching frequency Hz - 0.5
Includes short circuit protection XZ03.7 to XZ03.8 (output to control the motor
holding brake)
Motor holding brake: Installation instructions
Make sure the power supply is sufficient for the motor holding brake at the
motor. Take into account that voltage drops on the supply line. Use connection
lines with the largest possible cross section of single strands.
Use an external contact element in accordance with the required safety cate-
gory if you wish to supply motor holding brakes with higher currents than
the current load allowed at the connection point. Make sure to comply with
the required minimum current consumption of 100 mA when using an external
contact element. Otherwise the brake current monitor will signal an error.