Fan Motor Options
14.1.2 Constant Torque Motor Performance Data—Horizontal Configuration
Model Tap #
Default Factory
Motor Setting
CFM
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
RF007
1 FO 208 188 167 — — — — — — — — —
2 DH 304 290 276 263 248 233 221 — — — — —
3 FL 344 331 320 308 295 283 270 — — — — —
4 441 431 420 411 402 392 382 — — — — —
RF009
1 FO 228 204 181 — — — — — — — — —
2 DH 337 321 304 289 272 257 244 — — — — —
3 FL 377 363 348 334 320 304 291 — — — — —
4 465 453 441 429 417 405 394 — — — — —
RF012
1 FO 282 265 246 227 211 — — — — — — —
2 DH 402 389 377 364 350 338 323 311 — — — —
3 FL 442 428 416 403 392 381 368 356 — — — —
4 541 531 519 507 493 474 449 422 — — — —
Note: DH = Dehumidification, FL = Full Load, and FO = Fan Only
Table 13 Constant Torque Motor Performance Data—Horizontal Configuration
Off delay = 30 seconds = After receiving an OFF command
motor will continue running for 30 seconds. CFM based on
wet coil and 1" Merv 5 Throwaway. DH is the default tap for
Dehumidification.
| 39