Safety instructions | RG8.0 / RG4.0 | 27 en
R Some refrigerant may not be used in environments
with a risk of explosion. Fire, naked flames and
smoking are prohibited. No welding or soldering is
allowed. High temperatures and UV radiation may
cause refrigerant to chemically separate. The result-
ing products cause cough and nausea.
R Refrigerants should never be mixed within a system.
Comply with your local regulations for handling and
storing of recovered refrigerant.
R Additionally, recovery tanks should always be placed
on a refrigerant scale to monitor the filled quantity.
R Use only approved tanks with a minimum of 41bar
working pressure that comply with local regulations.
R Recovery tanks are designed for different pressures.
Do not exceed the working pressure of each tank.
R Never transport an overfilled tank. Safety codes rec-
ommend that hermetically sealed tanks should not
be filled more than 80% of its capacity with liquid.
The remaining 20% is called head pressure room.
Refrigerant expands when temperature increases
and may cause a tank to explode if overfilled. Refer
to the following table:
Tank
temperature
16 °C 21 °C 38 °C 54 °C 66 °C
Refrigerant vol-
ume varying be-
tween 80% to
94% in the tank
Space occu-
pied by liquid
80% 81% 83% 90% 94%
Refrigerant vol-
ume varying be-
tween 90% to
full in the tank
Space occu-
pied by liquid
90% 92% 96% 100%
Explo-
sion
Danger: Risk of explosion
The pressure switch does not prevent over-
filling of a tank. If the RG8.0 / RG4.0 stops
due to high pressure, the tank might be
completely filled and can lead to explosion.
¶ Do not overfill the tank.
¶ Ensure that you monitor the weighing
scale regularly.
R A scale must be used to avoid overfilling the storage
tank.
R Cover the ports of the storage tank with caps to
prevent refrigerant leakage.
R Tanks and filters should be designated for one refrig-
erant only and clearly marked as to which refriger-
ant they contain and/or are designated for use with.
Refrigerants should never be mixed within a system.
Comply with your local regulations for handling and
storing of recovered refrigerant.
R Special care should be taken when recovering from a
burned-out compressor. Use two high capacity acid
filters, in series. Bosch recommends using
Alco®typeEK-162-F or Sporlan® type C-162-F.
R The RG8.0 / RG4.0 can be used only in a sheltered or
indoor environment.
3.1 Safety devices
R Pressure switch - Cuts off the power supply to the
motor if the normaloperating pressureexceeds
38.5bar.
R Circuit breaker - Terminates the power supply in
case of over current drawn by the RG8.0 / RG4.0 .