3 12 Heater Break Alarm3 12 Heater Break Alarm
A current transformer ( parts No. ) should be installed to detect the
heater current if a heater break alarm is required. The CT signal is sent to
input 2, and the PV2 will indicate the heater current in 0.1 Amp. resolution.
The range of current transformer is 0 to 50.0 Amp.
For more detailed descriptions about heater current monitoring, please see
CT94-1
Section 3-25.
A current transformer ( parts No. ) should be installed to detect the
heater
current if a heater break alarm is required. The CT signal is sent to
input
2, and the PV2 will indicate the heater current in 0.1 Amp. resolution.
The
range of current transformer is 0 to 50.0 Amp.
For
more detailed descriptions about heater current monitoring, please see
CT94-1
Section
3-25.
Example:
A furnace uses two 2KW heaters connected in parallel to warm up the process.
The line voltage is 220V and the rating current for each heater is 9.09A. If we
want to detect any one heater break, set A1SP=13.0A, A1HY=0.1
A1FN=PV2.L, A1MD=NORM, then
Example:
A
furnace uses two 2KW heaters connected in parallel to warm up the process.
The
line voltage is 220V and the rating current for each heater is 9.09A. If we
want
to detect any one heater break, set A1SP=13.0A, A1HY=0.1
A1FN=PV2.L,
A1MD=NORM, then
Heater Break Alarm 1
Setup : IN2 = CT
A1FN = PV2.L
A1MD = NORM
A1HY = 0.1
Adjust : A1SP
Trigger levels : A1SP 1/2 A1HYA
Heater Break Alarm 1
Setup
: IN2 = CT
A1FN
= PV2.L
A1MD
= NORM
A1HY
= 0.1
Adjust
: A1SP
Trigger
levels : A1SP 1/2 A1HYA
Limitations :
1. Linear output can't use heater break
alarm.
2. CYC1 should use 1 second or
longer to detect heater current reliably.
Limitations :
1.
Linear output can't use heater break
alarm.
2.
CYC1 should use 1 second or
longer
to detect heater current reliably.
0
10
20 30
40
50
A
0
10
20 30
40
50
A
0
10
20 30
40
50
A
No heater breaksNo heater breaks 1 heater breaks1 heater breaks 2 heaters breaks2 heaters breaks
Alarm !Alarm !
Alarm !Alarm !
Figure 3.17
Heater Break Alarm
Figure 3.17
Heater
Break Alarm
Heater Break Alarm 2
Setup : IN2 = CT
A2FN = PV2.L
A2MD = NORM
A2HY = 0.1
Adjust : A2SP
Trigger levels : A2SP 1/2 A2HYA
Heater Break Alarm 2
Setup
: IN2 = CT
A2FN
= PV2.L
A2MD
= NORM
A2HY
= 0.1
Adjust
: A2SP
Trigger
levels : A2SP 1/2 A2HYA
52
UM25001C