EasyManua.ls Logo

Brainchild BTC-2500 - Sensor Break Alarm; SP1 Range

Brainchild BTC-2500
142 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
315SP1Range3 15 SP1 Range
3 14 Sensor Break Alarm3 14 Sensor Break Alarm
SP1L ( SP1 low limit value ) and SP1H ( SP1 high limit value ) in setup menu
are used to confine the adjustment range of SP1.
SP1L ( SP1 low limit value ) and SP1H ( SP1 high limit value ) in setup menu
are
used to confine the adjustment range of SP1.
Example : A freezer is working in its normal temperature range -10 C to -15 C.
In order to avoid an abnormal set point, SP1L and SP1H are set with the
following values:
SP1L = -15 C SP1H = -10 C
Now SP1 can only be adjusted within the range from -10 C to -15 C.
Example : A freezer is working in its normal temperature range -10 C to -15 C.
In
order to avoid an abnormal set point, SP1L and SP1H are set with the
following
values:
SP1L
= -15 C SP1H = -10 C
Now
SP1 can only be adjusted within the range from -10 C to -15 C.
SP1
IN1H ( or sensor range high )IN1H ( or sensor range high )
SP1H
SP1L
IN1L ( or sensor range low )
IN1L ( or sensor range low )
Figure 3.19 SP1 RangeFigure 3.19 SP1 Range
Setup : SP1L, SP1HSetup : SP1L, SP1H
54
UM25001C
Alarm 1 or alarm 2 can be configured as sensor break alarm by selecting SENB
for A1FN or A2FN. If alarm 2 is required for sensor break alarm, then
OUT2 should be selected with =AL2.
The sensor break alarm is activated as soon as failure mode occurs. Refer to
for failure mode conditions. Note that also creates a
sensor break alarm. TIME,A1SP, A1DV, and A1HY are hidden if alarm 1 is
configured as a sensor break alarm. Similarly, TIME, A2SP, A2DV and A2HY are
hidden if alarm 2 is configured as a sensor break alarm.
One of 4 kinds of alarm modes can be selected for sensor break alarm. These
are: Normal alarm, Latching alarm, Holding alarm and Latching/Holding alarm.
However, the Holding alarm and Latching/Holding alarm are not recommended
to be chosen for sensor break alarm
See
for the descriptions of these alarm modes.
Section 3-17 A-D failure
Section 3-9
since sensor break alarm will not perform
holding function even if it is set with holding or latching/holding mode.
Alarm 1 or alarm 2 can be configured as sensor break alarm by selecting SENB
for
A1FN or A2FN. If alarm 2 is required for sensor break alarm, then
OUT2
should be selected with =AL2.
The
sensor break alarm is activated as soon as failure mode occurs. Refer to
for
failure mode conditions. Note that also creates a
sensor
break alarm. TIME,A1SP, A1DV, and A1HY are hidden if alarm 1 is
configured
as a sensor break alarm. Similarly, TIME, A2SP, A2DV and A2HY are
hidden
if alarm 2 is configured as a sensor break alarm.
One
of 4 kinds of alarm modes can be selected for sensor break alarm. These
are:
Normal alarm, Latching alarm, Holding alarm and Latching/Holding alarm.
However,
the Holding alarm and Latching/Holding alarm are not recommended
to
be chosen for sensor break alarm
See
for
the descriptions of these alarm modes.
Section
3-17 A-D failure
Section
3-9
since
sensor break alarm will not perform
holding
function even if it is set with holding or latching/holding mode.
Sensor Break Alarm 1
Setup:
Hidden:
Sensor Break Alarm 2
Setup:
Hidden:
A1FN=SENB
A1MD=NORM, LTCH
TIME, A1SP, A1DV
A1HY
OUT2= =AL2
A2FN=SENB
A2MD=NORM, LTCH
TIME , A2SP, A2DV
A2HY
Sensor Break Alarm 1
Setup:
Hidden:
Sensor
Break Alarm 2
Setup:
Hidden:
A1FN=SENB
A1MD=NORM,
LTCH
TIME,
A1SP, A1DV
A1HY
OUT2=
=AL2
A2FN=SENB
A2MD=NORM,
LTCH
TIME
, A2SP, A2DV
A2HY

Table of Contents

Related product manuals