EasyManuals Logo

Brivis ZonePlus B061006 User Manual

Brivis ZonePlus B061006
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
13
Setting Sensor Identification on an NC-6 when
used as a Slave (refer Table 4. example)
Determine which NC-6 Controller will be the Master and
which one will be the Slave
Mount the proposed NC-6 Slave onto the backing plate of
the NC-6 that has power supplied directly from the heater
control board
Change the NC-6 Slave identification number to “3” by
accessing Installer Parameters (see 6.3, p.14)
Fit the NC-6 Slave to its designated zone backing plate only
after the unit ID has been changed
Mount the Master Controller onto its backing plate – this will
not require a unit ID change
Once an NC-6 has been designated a ‘Slave’, Installer
Parameters will no longer be accessible from this NC-6.
The Master Controller must then be used to access the
installer parameters
6.2.2 ZonePlus with all NC-6 Controllers
All NC-6 controllers that are used in place of NT-1 sensors
must have their sensor ID altered so that it operates as a slave.
Important Notes:
Only the NC-6 Controller backing plates should be wired
and installed
Power up the system in the following sequence:
516 Network Module (if applicable)
N-PM1 Power Module (if applicable)
Heater
Cooling System (if applicable)
Table 5: 4-Zone System Using All NC-6 Controllers
(example)
Zone ID
Sensor
Type
Function
Unit ID
Factory
Setting
Unit ID
System
Setting
Zone A NC-6 Master “n01” “n01”
Zone B NC-6 Slave “n01” “n02”
Zone C NC-6 Slave “n01” “n03”
Zone D NC-6 Slave “n01” “n04”
Always set and record all parameters in the Appendix.
Setting Sensor Identification on an NC-6 when
all are used as Slaves (refer Table 5. example)
Determine which NC-6 Controller will be the Master and
which ones will be Slaves
Mount one of the proposed NC-6 Slaves onto the backing
plate of the NC-6 that has power supplied directly from the
heater control board
Change the NC-6 ID number to “2” by accessing Installer
Parameters (see 6.3, p.14)
Repeat for the remaining two Slaves and set unit ID to “3”
and “4” respectively
Fit the NC-6 Slaves to their designated zone backing plates
only after all unit ID have been changed
Mount the Master Controller onto its backing plate – this will
not require a unit ID change
Once an NC-6 has been designated a ‘Slave’, Installer
Parameters will no longer be accessible from this NC-6.
The Master Controller must then be used to access the
installer parameters

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brivis ZonePlus B061006 and is the answer not in the manual?

Brivis ZonePlus B061006 Specifications

General IconGeneral
BrandBrivis
ModelZonePlus B061006
CategoryController
LanguageEnglish