Table 8: Master Controller Parameters Cont’d
Parameter ID
Number and
Value (default)
Installer Parameter Description Installer Parameter
Value Settings
Please record
the values you
have set
n01 ID23:0 Heating Zone C - Unit Heater ID No.
n01 ID24:3 Heating Zone C - Relay Relay No. 1 to 4
n01 ID25:1 Heating Zone C - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID26:0 Heating Zone D - Unit Heater ID No.
n01 ID27:4 Heating Zone D - Relay Relay No. 1 to 4
n01 ID28:1 Heating Zone D - Temperature Sensing ID No. Sensor No. 1 to 4
n01 ID43:0 Heating - OFF Cycle Circulation Fan Operation 0 = OFF; 1 = ON
n01 ID73:1 Equipment Service Notification Message 0 = OFF; 1 = AUST; 2 = NZ
n01 ID92:0 Multi Set Point Control - Enable 0 = OFF; 1 = ON
n01 ID93:1 Refrig - Cooling Zone to Force Open 0 = None; 1=A; 2=B; 3=C; 4=D
n01 ID105:0 Heating - Enable Fan Scaling 0 = OFF; 1 = ON
n01 ID106:1 Heating - Common Zone Fan Speed Range = 1 to 16
n01 ID107:1 Heating - Zone A Fan Speed Range = 1 to 16
n01 ID108:1 Heating - Zone B Fan Speed Range = 1 to 16
n01 ID109:1 Heating - Zone C Fan Speed Range = 1 to 16
n01 ID110:1 Heating - Zone D Fan Speed Range = 1 to 16
n01 ID111:0 Refrig - Enable Fan Scaling 0 = OFF; 1 = ON
n01 ID112:1 Refrig - Common Zone Fan Speed Range = 1 to 16
n01 ID113:1 Refrig - Zone A Fan Speed Range = 1 to 16
n01 ID114:1 Refrig - Zone B Fan Speed Range = 1 to 16
n01 ID115:1 Refrig - Zone C Fan Speed Range = 1 to 16
n01 ID116:1 Refrig - Zone D Fan Speed Range = 1 to 16