XT-70 Control Panel 48
E2 Parameters Definition:
3 = Highest of Pile 1H or Pile 2H
Any other number will average Pile 1H and Pile 2H
The default setting is 1.
DOOR CLOSE POS This parameter is used on a single door to read the feedback potentiometer and
calculate the door position. This is a DC voltage. This parameter applies
primarily to Suberizer doors. See app note 21 for details.
DOOR OPEN POS This parameter is used on a single door to read the feedback potentiometer and
calculate the door position. This is a DC voltage. This parameter applies
primarily to Suberizer Doors. See app note 21 for details.
PILE H TIMER Pile Humidity Sensor Fail Timer. This is a Onion parameter and applies only to
the MVG onion program. If a pile humidity sensor were to fail, this timer would
have to time out before a Pile Humidity Fail Alarm would be active. The default
setting is 0 minutes and a 0 setting will disable the alarm.
PILE T TIMER Pile Temperature Sensor Fail Timer. This is a Onion parameter and applies
only to the MVG onion program. If a pile temperature sensor were to fail, this
timer would have to time out before a Pile Humidity Fail Alarm would be active.
The default setting is 0 minutes and a 0 setting will disable the alarm.
HUMID CONFIG / OSA MAX Humidity Config. A zero setting is normal. A setting of one will average the ple
num humidity sensor and the return humidity sensor. A setting of two will
activate the CSS calculated humidity output. Outside Air Temperature Max.
This is a Onion parameter and applies only to the MVG onion program. If the
outside air temperature exceeds this value, then the system will be forced into
STANDBY.
DH_DIFF Dehumid Differential. This setting will make sure the OSA is cold enough to be
dry air. A typical setting would be 5 to 10 degrees. This setting is in 1/10
of a degree. For 5°, set to 50. A zero setting will disable this feature.
The Aux1_cfg would have to be set to 2 for this to be active. See the potato
dehumid flow chart for more details.
PILE T CFG / Humid Diff The Pile Temperature Config is a Onion parameter and applies to the MVG
onion program only. This parameter is used to determine which of the pile
temperature sensors is used for control.
1 = Pile 1 Temperature
2 = Pile 2 Temperature
3 = Pile 3 Temperature
4 = Pile 4 Temperature
12 = Average of Pile 1 & 2
13 = Average of Pile 1 & 3
14 = Average of Pile 1 & 4
23 = Average of Pile 2 & 3
24 = Average of Pile 2 & 4
34 = Average of Pile 3 & 4