XT-70 Control Panel 50
E2 Parameters Definition:
PILE_5 Calibration constant for PILE 5 sensor. Example - lower value by .6 F. Enter
-6 for the value. Example - increase value by 1.6F. Enter 16 for the value.
PILE_6 Calibration constant for PILE 6 sensor. Example - lower value by .6 F. Enter
-6 for the value. Example - increase value by 1.6F. Enter 16 for the value.
PILE_7 Calibration constant for PILE 7 sensor. Example - lower value by .6 F. Enter
-6 for the value. Example - increase value by 1.6F. Enter 16 for the value.
PILE_8 Calibration constant for PILE 8 sensor. Example - lower value by .6 F. Enter
-6 for the value. Example - increase value by 1.6F. Enter 16 for the value.
OSA_H Calibration constant for OSA H sensor. Example - lower value by .6 %. Enter
-6 for the value. Example - increase value by 1.6%. Enter 16 for the value.
RTN_H Calibration constant for RTN H sensor. Example - lower value by .6 %. Enter
-6 for the value. Example - increase value by 1.6 %. Enter 16 for the value.
CO2 Calibration constant for CO2 sensor. Example - lower value by 6 ppm. Enter
-6 for the value. Example - increase value by 16ppm. Enter 16 for the value.