ALARM COUNT
This macro nags you every hour until you respond to the fact that there are 10 or more alarms. This could be
set to run at startup so it is always on. During maintenance you could stop it manually.
1
If alarm count on site "BURK-FM" < 10, goto line 1
2
Send email message “more than 10 alarms!” to email
list "Chief"
3
Wait for 01:00:00
4
Goto line 1
TRANSMITTER START SEQUENCE
Here is a tube transmitter startup that skips the filament turn on and delay if filaments are already on.
1
If status of "TX-A FIL ON / TX-A TX-A FIL OFF" on
site "BURK-FM" = "TX-A FIL ON", goto line 4
2
Raise "TX-A FIL ON" on site "BURK-FM" for
[default]
3
Wait for 00:05:00
4
Raise "TX-A RF ON" on site "BURK-FM" for
[default]
5
End macro